Bee Cave, TX case study · March 2026
Shared kitchen line backing up a Bee Cave retail center
Commercial property manager · Open-air retail center, Bee Cave near the Galleria · Sewer Jetting & CCTV Verification


Drag the divider to compare. Before: Sewer camera view of a Bee Cave shared restaurant sewer line narrowed by hardened grease before jetting After: Sewer camera view of the same Bee Cave shared line jetted back to full diameter with clean pipe walls
- Run cleaned
- 55 ft
- Diameter restored
- 100 pct
- Tenant closures
- 0
- Backups since
- 0
The problem on this Bee Cave site
Three restaurant tenants shared one 6-inch line to the street. Backups landed in the end-cap suite every few weeks, always during service, and the manager had no way to show which tenant was loading the line.
How our NASSCO-certified crew approached it
- Scoped the shared run before quoting cleaning so the cause was documented, not assumed
- Jetted upstream to downstream overnight with a rotating nozzle sized to the 6-inch line
- Pulled a verification scope with footage marks tied to each tenant tie-in
- Set an interval from the measured grease loading rather than a generic quarterly default
What the camera documented
- Hardened grease reducing the shared line to about a third of its diameter over a 55 ft run
- Heaviest loading immediately downstream of one tenant tie-in, captured on video with footage marks
- One interceptor riser lid seated wrong, letting solids carry over into the line
- Pipe itself structurally sound, no PACP structural defects logged
Measurable results
- Line restored to full diameter in one overnight window with no tenant closures
- Footage-marked evidence supported a cost allocation conversation with the responsible tenant
- Backup calls at the end-cap suite dropped to zero across the following two quarters
Need this on your Bee Cave project?
CSC Pipe Inspection runs commercial CCTV, jetting, hydro excavation and line locating across Austin and Central Texas with 25+ years of field experience and NASSCO/PACP-coded reporting.
More documented jobs
- Austin, TX · Sewer Jetting & CCTV VerificationGrease-choked 6-inch main serving a downtown Austin food hall
- Pflugerville, TX · Storm Drain Inspection & CleaningSilted storm culvert flooding a Pflugerville truck court
- Kyle, TX · Sewer Jetting & CCTV InspectionRepeat backups at a Kyle multifamily common line